Condor Pressure Control GmbH
Controls & Solutions

HOME


ONLINE SHOP


IMPRINT

Certificate ISO 9001, klein

Electronic level switch ENR
Electronic level switch for all ranges from 0.1 – 2 m
For panel board mounting
Measurement according to impact pressure method
Relay output
Output signal: 0 – 10 V

 

Electronic level switch with integrated relative pressure transformer for panel board mounting, quick-connect for pneumatic tube, two adjustable thresholds, relay output and isolating transformer according to VDE 0550.

Function: The device evaluates the pressure applied to the sensor. Should a pump for emptying a tank be connected to terminals 11 and 12, then the pump is switched on when the upper threshold is exceeded. The pump is switched off when falling below the lower threshold. Both thresholds are adjustable. The LED illuminates when the pump is running, whereby the relay is deactivated.

 

 

ENR 2


Technical Data
Measuring range: 0,1 - 2 m
Max. perm. Level: 10 m
Output signal: 0 - 10 V

  0 V = 0,1 m / 10 V = measuring range end value
Operating voltage: 230 V AC

 

 

 